Specifications

4 - 9
(2) RECV instruction
(Network No. designation)
JP.RECV
JP: Executed at startup
Receive command
Jn (S1) (D1) (D2)
(Network module start I/O No. designation)
GP.RECV
GP: Executed at startup
Receive command
Un (S1) (D1) (D2)
Description of setting Setting range
Jn Host's network No.
1 to 239
254: Network number designated with
valid module during other station
access
Un
Start I/O number of the host's network module
Designate the higher two digits of the 3-digit I/O number.
0 to FE
H
(S1)
Control data storage head device
Designate the head device of the host that stores the control
data.
Word device *
2
(D1)
Receive data storage head device
Designate the head device of the host that stores the
receive data.
Word device *
2
(D2)
Receive completion device
Designate a device to be turned on for one scan upon
receive completion.
(D2)............ OFF: Not completed ON: Complete
(D2) + 1...... OFF: Normal ON: Abnormal
Bit device *
1
Bit designation of word device *
3
*1: Bit device : X, Y, M, L, F, V, and B
*2: Word device : T, C, D, W, ST, R, and ZR
*3: Bit designation of word device : Word device, bit number
(Configuration of the control data (S1))
For the detailed description of each item, refer to the next page.
Data set
Device
Item
User
(when executed)
System
(when completed)
(S1) Execution/abnormal completion type
(S1) + 1 Completion status
(S1) + 2 Host storage channel
(S1) + 3 Channel used by the sending station
(S1) + 4 Sending station network No.
(S1) + 5 Sending station number
(S1) + 6 (Use prohibited)
(S1) + 7 Number of resends
(S1) + 8 Arrival monitoring time
(S1) + 9 Receive data length
(S1) + 10 (Use prohibited)
(S1) + 11 Clock set flag
(S1) + 12 Year (lower two digits)/month of
abnormal completion
(S1) + 13 Date/hour of abnormal completion
(S1) + 14 Minute/second of abnormal completion
(S1) + 15 Year (higher two digits)/day of the
week of abnormal completion
(S1) + 16 Abnormal detection network No.
(S1) + 17 Abnormal detection station number
Used when abnormal
completion type is set
to "With clock data
setting".
*1: Set by sequence program.
*2: Stored when instruction is completed.