Specifications

4 - 6
Detailed description of the control data
Device Item Description
(S1)
Execution/abnormal
completion type
b15 b7 b0
0
2) 1)
0
to to
1) Execution type (bit 0)
0: No arrival confirmation
When the target station is on the local network : Completed when data is sent from the
host.
Execution
source
Target
station
Complete
When the target station is on the other network : Completed when the data arrives at
the relay station on the network of
the local station.
Execution
source
Relay
station
Complete
Target
station
1: With arrival confirmation
Completed when the data is stored in the target station's designated channel.
Execution
source
Relay
station
Complete
Target
station
Target
station
2) Abnormal completion type (bit 7)
Sets the clock data set status at abnormal completion.
0: Does not set the clock data : Does not store the clock data at error
occurrence in (S1) + 11 to (S1) + 17.
1: Sets the clock data : Stores the clock data at error occurrence
in (S1) + 11 to (S1) + 17.
(S1) + 1 Completion status
Stores the status when an instruction is completed.
0 : Normal
Other than 0 : Abnormal (Refer to Appendix 5 for error codes)
(S1) + 2 Channel used by the host
Designates the channel to be used by the host.
1 to 8 (channels)
(S1) + 3
Target station storage
channel
(logical channel No.)
Designates the target station's channel to store the data.
1 to 64 (logical channel)
(S1) + 4 Target station network No.
Designates the network No. of the target station.
1 to 239 : Network No.
254 : Designates with the parameter setting, "Valid module during other station
access" setting, when 254 is designated in Jn.