Specifications
4 - 4
(2) Setting method
Set the logical channel numbers in the link special registers (SW8 to SWF) with
the sequence program.
SW No. Name Valid setting range Default
SW8 Logical channel setting (channel 1) 1 to 64 0: (Logical channel 1) *
2
SW9 Logical channel setting (channel 2) 1 to 64 0: (Logical channel 2) *
2
SWA Logical channel setting (channel 3) 1 to 64 0: (Logical channel 3) *
2
SWB Logical channel setting (channel 4) 1 to 64 0: (Logical channel 4) *
2
SWC Logical channel setting (channel 5) 1 to 64 0: (Logical channel 5) *
2
SWD Logical channel setting (channel 6) 1 to 64 0: (Logical channel 6) *
2
SWE Logical channel setting (channel 7) 1 to 64 0: (Logical channel 7) *
2
SWF Logical channel setting (channel 8) 1 to 64 0: (Logical channel 8) *
2
*2: The logical channel number is processed as the actual channel number when "0" is set.
(3) Transient transmission instruction that allows the logical channel designation
No. Instruction Description
1 SEND Sends data