Specifications

App - 93
(Example) When setting the [Maximum No. of transients in 1 scan] of [Transient setting]
to one.
Start
Fixed term cycle interval setting time
1linkscan
1
1linkscan
Low
2 3 4 1 2 3 4 1 2 3
Fixed term cycle interval setting time
1linkscan
1
1linkscan
2 3 4 1 2 3 4 1 2 3
1linkscan
1 2 3 4
Data link of the
control station
Low-speed cyclic
Normal link scan
Transmission data
Low Low Low
(3) System timer interval
The low-speed cyclic data is sent in the link cycle at the designated time.
By omitting year, month, and date, the low-speed cycle transmission can be
activated yearly (or monthly, or daily). Hour, minute and second cannot be omitted.
Setting points: 1 to 8 points
[Setting method]
1) Click System times
to select.
2) Set year, month, date, hour, minute and second to the designated time.
In the following screen example:
Points 1 to 3 : By omitting year, month and date, data is sent every day
at the designated time.
Points 4 and 5 : By omitting year and month, data is sent at the designated
time monthly.
Point 6 : By omitting the year, data is sent at the designated time
every year.
Points 7 and 8 : Data is sent only once at the designated time.
POINT
(1) The system timer operates based on the host's clock. If used without matching the
clocks on the sending station and receiving station, there may be a time gap
between the stations.
(2) When handling multiple data without the block guarantee function per station
, new
and old data may coexist. Apply interlocks in the programs.