Specifications
App - 78
(Configuration of the control data (S1))
Data set
Device Item
User
(when executed)*
1
System
(when completed)*
2
(S1) Execution/abnormal completion type
(S1) + 1 Completion status
(S1) + 2 Host storage channel
(S1) + 3 Channel used by the sending station
(S1) + 4 Sending station network No.
(S1) + 5 Sending station number
(S1) + 6 (Use prohibited) — —
(S1) + 7 (Use prohibited) — —
(S1) + 8 (Use prohibited) — —
(S1) + 9 Receive data length
(S1) + 10 (Use prohibited) — —
*1: Items set by the sequence program
*2: Items stored when the instruction is completed
Detailed description of the control data
Device Item Description
(S1) Abnormal completion type
0100 0
b15 b8 b7 b6 b0toto
1) Abnormal completion type (bit 7)
Sets the clock data set status at abnormal completion.
0: Does not set the clock data: Do not store the clock data at error occurrence
in (S1) + 11 to (S1) + 15.
1: Sets the clock data : Stores the clock data at error occurrence in
(S1) + 11 to (S1) 15.
(S1) + 1 Completion status
Stores the status at the instruction completion.
0: Normal completion
(S1) + 2 Host storage channel
Designates the channel that stores the data to be read.
1 to 8 (channels)
(S1) + 3
Channel used by the sending
station
Stores the channel used by the sending station.
1 to 8 (channels)
(S1) + 4 Sending station network No.
Stores the network No. of the sending station.
1 to 239: Network No.
(S1) + 5 Sending station number
Stores the station number of the sending station.
1 to 64: Station number
(S1) + 6 (Use prohibited) —
(S1) + 7 (Use prohibited) —
(S1) + 8 (Use prohibited) —
(S1) + 9 Receive data length
Stores the receive data count stored in (D1) to (D1) + n.
1 to 480 (words)
(S1) + 10 (Use prohibited) —