Specifications
App - 72
REMARK
The correspondence between the interrupt (SI) No. of the network module and the
interrupt pointer (I
) *
1
on the CPU side are set on the PLC system setting screen in
the PLC parameters as shown below.
The following shows how to set these parameters on the PLC system setting screen
using the interrupt setting parameters shown on the previous page.
The interrupt (SI) No. (0 to 6) of the network module side are assigned to the interrupt
pointers (I50 to I56) of the CPU side.
The following setting is taken as an example.
<Intelligent module side>
(1) Start I/O No. : 0000 ......... Network module installation position
(2) Start SI No. : 0 ............... Start number (0 to 6) of interrupt (SI) number
<CPU side>
(1) Interrupt pointer start No. : 50….Start No. (I50 to I56) of the interrupt program
(2) Interrupt pointer count : 7……Number of interrupt setting conditions
CPU side
Interrupt
pointer (I50)
Network
module side
Interrupt (SI) No.
*1: Number used for the actual interrupt program (I )