Specifications
App - 71
Appendix 8.1 Interrupt setting parameters
The maximum of 16 interrupt conditions can be set for each device code of the interrupt
setting conditions on the following setting screen.
button to display the setting screen.
Click the
(Selections of the interrupt conditions for interrupt device codes and the valid setting ranges)
Setting condition
Device code
Device
No.
Detection method Interrupt condition
Word device
setting value
Channel
No./connection
No.
Interrupt
(SI) No.
RECVS — Edge detection fixed
Scan completion fixed
An interrupt occurs when the
designated channel receives
data.
— 1 to 8 0 to 15
LB
0 to
3FFF
H
— — 0 to 15
LX
0 to
1FFF
H
— — 0 to 15
SB
0 to
1FF
H
Edge detection/level detection + on/off
An interrupt occurs under the following conditions:
At on : (on + level *
1
)
At off : (off + level *
1
)
At rise : (on + edge)
At fall : (off + edge)
— — 0 to 15
LW
0 to
3FFF
H
0 to 65535 — 0 to 15
SW
0 to
1FF
H
Edge detection/level detection + equal to/not equal to
An interrupt occurs under the following conditions:
Values match : (equal to + level *
1
)
Values mismatch : (not equal to + level *
1
)
Values match (only for the first time) :
(equal to + edge)
Values mismatch (only for the first time) :
(not equal to + edge)
0 to 65535 — 0 to 15
Scan completion *
2
— — — — — 0 to 15
*1: When the level detection is selected as the detection method, an interrupt occurs after the designated device's level condition is checked
for each link scan of the set network module.
*2: When the scan completion is selected, an interrupt occurs for each link scan of the set network module.