Specifications

App - 63
Error Code
(SD0) *
1
Error Contents and Cause Corrective Action
Applicable
CPU
3400
The head I/O number of the target module in the remote password
file is set to other than 0H to 0FF0H.
Change the head I/O number of the target module to within
the 0H to 0FF0H range.
The position specified as the head I/O number of the remote
password file is incorrect due to one of the following reasons:
• Module is not mounted.
Other than the Q corresponding intelligent function module (I/O, A,
QnA module)
Intelligent function module other than the QJ71C24 (-R2) and
QJ71E71 (-B2).
• QJ71C24 (-R2) and QJ71E71 (-B2) of function version A.
Mount QJ71C24 (-R2) or QJ71E71 (-B2) of function version
B in the position specified as the head I/O No. of the remote
password file.
3401
QJ71C24 (-R2) or QJ71E71 (-B2) of function version B under control
of another CPU was specified in a multiple CPU system.
(1) Change it to the QJ71C24 (-R2) or QJ71E71 (-B2) of
function version A under control of the host CPU.
(2) Delete the remote password setting.
QCPU
function
Ver. B or
later
4000 The program contains an instruction code that cannot be decoded.
4001
The program contains a dedicated instruction for SFC although it is
not an SFC program.
4002
The extension instruction designated in a program has an incorrect
instruction name.
The extension instruction designated in a program cannot be
executed by the designated module.
4003
The extension instruction designated in a program has an incorrect
number of devices.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
Rem
4004
The devices, which cannot be used in the extension instruction
designated in a program, are designated.
The double quotation "Un" is not described in the extension
instruction.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
Rem
4010 There is no END (FEND) instruction in the program.
4020
The total number of internal file pointers used in a program exceeds
the number of internal file pointers set in the parameters.
4021 The common pointer Nos. used for each file is overlapped.
4030 The interrupt pointer Nos. used for each file is overlapped.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
4100 The instruction contains the data that cannot be used.
4101
The number of data to be used by the instruction exceeds the
allowable range.
Alternatively, the storage data or constants of the devices designated
by the instruction exceed the allowable range.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
Rem
In a multiple CPU system, the link direct device (J G ) was
designated for the network module under control of another CPU.
(1) Delete from the program the link direct device which
designates the network module under control of another
CPU.
(2) Using the link direct device, designate the network
module under control of the host CPU.
QCPU
function
Ver. B or
later
4102
The network No. or station No. designated in the network dedicated
instruction is wrong.
The link direct device (J
W ) setting is incorrect.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
Rem
4103 The configuration of the PID dedicated instruction is incorrect.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
33 or more multiple CPU dedicated instructions were executed from
one CPU module.
Using the multiple CPU dedicated instruction completion bit,
provide interlocks to prevent one QCPU module from
executing 32 or more multiple CPU dedicated instructions.
QCPU
function
Ver. B or
later
4107
Number of the CC-Link instructions executed exceeds 64.
4108
The CC-Link parameter is not set when the CC-Link instruction is
executed.
Set the numbers of the CC-Link instructions to be executed
to 64 or less.
Execute the CC-Link instruction after setting the CC-Link
parameter.
QnA
NEXT instruction was not executed following the execution of FOR
instruction.
4200
Alternatively, there are fewer NEXT instructions than FOR
instructions.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
NEXT instruction was not executed although FOR instruction has not
been executed.
4201
Alternatively, there are more NEXT instructions than FOR
instructions.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
4202 More than 16 nesting levels are programmed. Set the nesting levels to16 or less.
4203
BREAK instruction was executed although FOR instruction has not
been executed.
Read the common information of the error using a
peripheral device, check the error step corresponding to its
numerical value (program error location), and correct the
problem.
*1: Characters in parentheses ( ) indicate the special register numbers where each information is being stored.