Specifications
App - 61
Error Code
(SD0) *
1
Error Contents and Cause Corrective Action
Applicable
CPU
3102
An error was occurred on the network module by result of network
parameter check.
The unique parameter for MELSECNET/H and MELSECNET/10 is
not correct.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
In a multiple CPU system, the QJ71E71 (-B2) under control of
another station is specified as the head I/O number of the Ethernet
setting parameter.
(1) Delete the Ethernet setting parameter of the QJ71E71
(-B2) under control of another station.
(2) Change the setting to the head I/O number of the
QJ71E71 (-B2) under control of the host CPU.
QCPU
function
Ver. B or
later
• Although the number of modules has been set to 1 or more in the
Ethernet module count setting parameter setting, the number of
actually mounted module is 0.
• The head I/O number of the Ethernet setting parameter differs from
the I/O number. of the actually mounted module.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
Rem
3103
AJ71QE71 does not exist in the position of I/O number set by the
parameter.
I/O number designation is overlapping.
Numbers of the parameter and actually mounted AJ71QE71 are
different.
Ethernet (parameter + dedicated instruction) is set to 5 or more.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
QnA
3104
Ethernet , MELSECNET/H and MELSECNET/10 use the same
network number.
Network number, station number or group number set by the
parameter is out of range.
The I/O No.is out of the using CPU range.
The contents of unique parameter for Ethernet are not correct.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
Rem
In a multiple CPU system, the QJ61BT11 under control of another
station is specified as the head I/O number of the CC-Link setting
parameter.
(1) Delete the CC-Link setting parameter of QJ61BT11
under control of another station.
(2) Change the setting to the head I/O number of the
QJ61BT11 under control of the host CPU.
QCPU
function
Ver. B or
later
(1) Although the number of modules has been set to 1 or more in the
CC-Link module count setting parameter setting, the number of
actually mounted module is 0.
(2) The head I/O number in the common parameters is different from
that of the actually mounted module.
(3) The station types for the CC-Link module count setting parameter
are mismatch.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
Rem
3105
The contents of the Ethernet parameter are not correct. Write and correct the parameters. QnA
The CC-Link refresh range exceeded the file register capacity.
Change the file register file to the one refresh-enabled in the
whole range.
QCPU
function
Ver. B or
later
3106
The network refresh parameter for CC-Link is out of range. Check the parameter setting.
QCPU
Rem
3107 The contents of CC-Link parameter are not correct. Check the parameter setting.
Rem
3200 The contents of parameter setting are illegal.
3201 The contents of SFC block adjunct information are illegal.
3202
The number of step relays specified in the parameter is less than that
used in the program.
3203
The execution type of the SFC program specified in the parameter is
other than scan execution.
Correct and write the parameters.
3300
The head I/O number in the intelligent function module parameter set
on GX Configurator differs from the actual mounted I/O number.
Check the parameter setting.
QCPU
Rem
3301
The link refresh range of the intelligent function module exceeded the
file register capacity.
Change the file register file to the one refresh-enabled in the
whole range.
QCPU
function
Ver. B or
later
3301 The refresh parameter of intelligent function module is out of range.
Check the parameter setting.
QCPU
Rem
3302 The parameter of intelligent function module is not correct. Check the parameter setting. QCPU
3303
In a multiple CPU system, automatic refresh setting or similar
parameter setting was made to the intelligent function module under
control of another CPU.
(1) Delete the automatic refresh setting or similar parameter
setting of the intelligent function module under control of
another CPU.
(2) Change the setting to the automatic refresh setting or
similar parameter setting of the intelligent function
module under control of the host CPU.
QCPU
function
Ver. B or
later
*1: Characters in parentheses ( ) indicate the special register numbers where each information is being stored.