Specifications
App - 59
Error Code
(SD0) *
1
Error Contents and Cause Corrective Action
Applicable
CPU
Automatic refresh range of the multiple CPU system exceeded the
file register capacity.
Change the file register file for the one refresh-enabled in
the whole range.
QCPU
function Ver.
B or later
3003
The number of device points set at the parameter device settings is
set in the range of the possible CPU module.
(1) Read the detailed information of the error using the
peripheral device, check the parameter items
corresponding to those numerical values (parameter
numbers), and correct when necessary.
(2) If the error is still generated following the correction of
the parameter settings, the possible cause is the
memory error of the CPU module's built-in RAM or the
memory card. Contact your nearest Mitsubishi
representative.
3004
The parameter file does not correspond to Q/QnACPU.
Alternatively, the contents of the file are not parameters.
Check whether the parameter file version is
. QPA,
and whether the file contents are parameters.
3009
In a multiple CPU system, the modules for A and QnA have been set
to multiple control CPUs.
Reset the parameter I/O allocation to control them under
one CPU module. (Change the parameters of all CPUs in
the multiple CPU system.)
3010
The parameter-set number of CPU modules differs from the actual
number in a multiple CPU system.
Match the number of (CPU modules in multiple CPU setting)
- (CPUs set as empty in I/O allocation) with that of actually
mounted CPU modules.
3012
Multiple CPU setting or control CPU setting differs from that of the
reference CPU in a multiple CPU system.
Match the multiple CPU setting or control CPU setting in the
parameter with that of the reference CPU (CPU No.1).
3013
Multiple CPU automatic refresh setting is any of the followings in a
multiple CPU system.
(1) When a bit device is specified as a refresh device, a number
other than a multiple of 16 is specified for the refresh starting
device.
(2) The device specified is other than the one that may be specified.
(3) The number of send points is an odd number.
Check the following in the multiple CPU automatic refresh
parameters and make correction.
(1) When specifying the bit device, specify a multiple of 16
for the refresh starting device.
(2) Specify the device that may be specified for the refresh
device.
(3) Set the number of send points to an even number.
QCPU
function
Ver. B or
later
In a multiple CPU system, the QJ71LP21/BR11 under control of
another CPU is specified as the head I/O number in the network
setting parameter of the MELSECNET/H.
(1) Delete the MELSECNET/10(H) network parameter of
the QJ71LP21/BR11 under control of another CPU.
(2) Change the setting to the head I/O number of the
QJ71LP21/BR11 under control of the host CPU.
The link parameters of the QJ71LP21/BR11 operating in the ordinary
station were rewritten to the control station, Or the link parameters of
the QJ71LP21/BR11 operating in the control station were rewritten to
the ordinary station.
(The link parameters are reflected on the module side by making a
reset.)
Reset the CPU module.
QCPU
function
Ver. B or
later
(1) The number of actually installed modules is different from that
designated in the number of modules setting parameter of
MELSECNET/H.
(2) The head I/O number of actually installed modules is different
from that of designated in the network setting parameter of
MELSECNET/H.
(3) Some data in the parameter cannot be handled.
(4) The station type of MELSECNET/H has been changed while the
power is on.
(Setting from RESET to RUN is required to change the station
type.)
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
QCPU
3100
Although the QnACPU is a control station or master station, the
network parameters have not been written.
(1) Correct and write the network parameters.
(2) If the error occurs after correction, it suggests a
hardware fault. Contact your nearest Mitsubishi
representative.
QnA
The link refresh range exceeded the file register capacity.
Change the file register file for the one refresh-enabled in
the whole range.
• When the station number of the MELSECNET/H module is 0, the
PLC to PLC network parameter setting has been made.
• When the station number of the MELSECNET/H module is other
than 0, the remote master parameter setting has been made.
Correct the type or station number of the MELSECNET/H
module in the parameter to meet the used system.
QCPU
function
Ver. B or
later
3101
The network No. specified by a parameter is different from that of the
actually mounted network.
The head I/O No. specified by a parameter is different from that of
the actually mounted network.
The network type specified by a parameter is different from that of
the actually mounted network.
The network refresh parameter of the MELSECNET/H and
MELSECNET/ 10 is out of the specified area.
Match the contents specified by a parameter to that of the
actually mounted.
*1: Characters in parentheses ( ) indicate the special register numbers where each information is being stored.