Specifications

App - 28
Special Relay List
(1) Diagnostic Information
Number Name Meaning Explanation
Set by
(When set)
Applicable
ACPU
M9
Applicable
CPU
SM0
Diagnostic
errors
OFF : No error
ON : Error
Turns ON if diagnosis results show error occurrence.
(Including the annunciator being ON and the detection
of an error by the CHK instruction.)
Stays ON subsequently even if normal operations are
restored
S (Error
occurrence)
New
SM1
Self-diagnostic
error
OFF : No self-diagnosis
errors
ON : Self-diagnosis
Turns ON when an error occurs as a result of
self-diagnosis. (Excluding the annunciator being ON
and the detection of an error by the CHK instruction.)
Stays ON subsequently even if normal operations
restored.
S (Error
occurrence)
M9008
SM5
Error common
information
OFF : No error common
information
ON : Error common
information
• , Turns ON if there is error common information when
SM0 is ON
S (Error
occurrence)
New
SM16
Error individual
information
OFF : No error common
information
ON : Error common
information
Turns ON if there is error individual information when
SM0 is ON
S (Error
occurrence)
New
SM50 Error reset OFF ON: Error reset Performs the error reset operation U New
+ Rem
SM60
Fuse blown
detection
OFF : Normal
ON : Module with fuse
blown
Turns ON even if there is only one output module with a
fuse blown, and remains ON even after returning to
normal
Fuse blown state is checked even for remote I/O station
output modules.
S (Error
occurrence)
M9000
SM61
I/O module
verification error
OFF : Normal
ON : Error
• Turns ON if there is a discrepancy between the actual
I/O modules and the registered information when the
power is turned on, and remains ON even after
returning to normal.
I/O module verification is also performed for remote I/O
station modules.
S (Error
occurrence)
M9002
+ Rem
SM120
Detection of
external power
supply OFF
OFF : Normal
ON : There is a module
whose external
power supply is OFF.
Turns ON when at least one module is in the status
where the external power supply is OFF. Remains ON
even after returning to normal.
*
Applicable only for Q-series modules. (For future use)
S (Error
occurrence)
New
QCPU
Rem
(2) System information
Number Name Meaning Explanation
Set by
(When set)
Applicable
ACPU
M9
Applicable
CPU
PAUSE enable
coil
OFF : PAUSE disabled
ON : PAUSE enabled
If this relay is ON when the remote PAUSE contact
turns ON, the PAUSE state is entered.
U M9040
SM206
Device test
request
acceptance
status
OFF : Device test not yet
executed
ON : Device test executed
Turns ON when the device test mode is executed on
GX Developer.
S (Request) New Rem
SM213
Clock data read
request
OFF : Ignored
ON : Read request
• When this relay is ON, the clock data is read to SD210
through SD213 as BCD values.
U M9028 + Rem
SM250
Max. loaded I/O
read
OFF : Ignored
ON : Read
When this relay turns from OFF to ON, the maximum
loaded I/O number is read to SD250.
U New + Rem
Turns ON when a CC-Link error is detected in any of
the installed QJ61QBT11. Turns OFF when normal
operation is restored.
S (Status
change)
New
QCPU
Rem
SM280 CC-Link error
OFF : Normal
ON : Error
Goes ON when a CC-Link error is detected in any of the
installed A(1S)J61QBT11. Stays ON even after the
normal operation is restored.
S (Error
occurrence)
New QnA
(3) Scan information
Number Name Meaning Explanation
Set by
(When set)
Applicable
ACPU
M9
Applicable
CPU
SM551
Reads module
service interval
OFF : Ignored
ON : Read
When this turns from OFF to ON, the module service
interval designated by SD550 is read to SD551 through
552.
U New
+ Rem