Specifications

App - 15
Link special register (SW) list (Continued)
Use permitted/prohibited
Control
station
Normal
station
Remote
master
station
Remote
I/O
station
Number Name Description
Optical
Coaxial
Optical
Coaxial
Optical
Coaxial
Optical
Coaxial
SW003B
(59)
Send/receive
instruction (6)
processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/REQ/RECVS/RRUN/
RSTOP/RTMRD/RTMWR/REMFR/REMTO instructions (when the physical channel 6 is
used).
0 : Normal completion
1 or more : Abnormal completion (Refer to Appendix 7.1 for error codes)
SW003D
(61)
Send/receive
instruction (7)
processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/REQ/RECVS/RRUN/
RSTOP/RTMRD/RTMWR/REMFR/REMTO instructions (when the physical channel 7 is
used).
0 : Normal completion
1 or more : Abnormal completion (Refer to Appendix 7.1 for error codes)
SW003F
(63)
Send/receive
instruction (8)
processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/REQ/RECVS/RRUN/
RSTOP/RTMRD/RTMWR/REMFR/REMTO instructions (when the physical channel 8 is
used).
0 : Normal completion
1 or more : Abnormal completion (Refer to Appendix 7.1 for error codes)
SW0040
(64)
Network No.
Stores the network number of the host.
Range: 1 to 239
SW0041
(65)
Group No.
Stores the group number of the host.
0 : No group designation
1 to 32 : Group No.
SW0042
(66)
Station No.
Stores the station number of the host.
Range : 1 to 64
SW0043
(67)
Mode status
Stores the mode status of the host.
0 : Online
2 : Offline
3 or more : Applicable test
SW0044
(68)
Station setting
Stores the condition setting switch status of the host.
0 : OFF
1 : ON
0to 9 87 32 1SW0044
b15
to
b8 b7 b6 b2 b1 b0
0
b9
Network type (PLC to PLC network)
Station type
(0: Normal station, 1: Control station)
Control station operation
(0: Switch to the designated control station,
1: Keep the current control station)
Operating mode
(0: Online mode, 1: Debug mode)
to
to
SW0046
(70)
Module type
Stores the network module type of the host.
00
SW0046
b15b14 b13 to b2 b1 b0
to
0: Duplex 1: Single
01: Optical 10: Coaxial 11: Twisted
0: Loop 1: Bus
SW0047
(71)
Baton pass
status
Stores the baton pass status of the host.
0 : Executing data linking
1 : Data linking stopped (instructed by other station)
2 : Data linking stopped (instructed by host)
3 : Executing baton pass (parameter received)
4 : Executing baton pass (parameter received)
5 : Executing baton pass (parameter not received)
6 : Being disconnected (no baton pass)
7 : Being disconnected (line error)
11
H
: Loop test
12
H
: Setup confirmation test
13
H
: Station order check test
14
H
: Communication test
1F
H
: Offline test