Specifications

App - 12
Link special relay (SB) list (Continued)
Use permitted/prohibited
Control
station
Normal
station
Remote
master
station
Remote
I/O
station
No. Name Description
Optical
Coaxial
O
ptical
Coaxial
Optical
Coaxial
Optical
Coaxial
*
3
SB00AC
(172)
Offline test instruction
Indicates the offline test instruction status.
Off: Not instructed
On: Instructed
*
3
SB00AD
(173)
Offline test completion
Indicates the offline test completion status.
OFF: Not completed
ON: Completed
*
3
SB00AE
(174)
Offline test response
designation
Indicates the offline test response status.
Off: No response
On: Responded
*
3
SB00AF
(175)
Offline test response
completion
Indicates the offline test response completion status.
Off: Response not completed
On: Response completed
*
3
SB00EE
(238)
Transient error
Indicates the transient transmission error status.
Off: No error
On: Error exists
*3: Valid only when SB0047 is off. When it turns on (error), the last data are retained.