Specifications
App - 3
Appendix 2 Differences between the QJ71LP21/QJ71LP21-25/QJ71BR11 and the
AJ71LP21/AJ71QBR11, A1SJ71QLP21/A1SJ71QBR11
Appendix 2.1 Differences in LED displays and switch settings
The MELSECNET/H network modules QJ71LP21, QJ71LP21-25 and QJ71BR11 have
the same LED displays and switch settings as those of the MELSECNET/10 network
modules AJ71QLP21, AJ71QBR11, A1SJ71QLP21 and A1SJ71QBR11. However,
each network module has the following differences from others as shown in the table
below. Please consider these differences when operating the network modules.
Model name
Item
QJ71LP21, QJ71LP21-25
QJ71BR21
AJ71QLP21 AJ71QBR11 A1SJ71QLP21 A1SJ71QBR11
RUN RUN RUN
— POWER (PW)
*1
— PC (PC)
*1
— REMOTE (REM.)
*1
— DUAL — DUAL —
MNG MNG, S.MNG MNG, S.MNG
T.PASS T.PASS T.PAS
D.LINK D.LINK D.LINK
SD SD SD
RD RD RD
ERR.
*2
SW.E.
M/S.E.
PRM.E.
CPU R/W
(SW.E.)
*1
(M/S.E.)
*1
(PRM.E.)
*1
CPU R/W
LED display
L ERR.
*2
CRC
OVER
AB.IF
TIME
DATA
UNDER
LOOP
CRC
OVER
AB.IF
TIME
DATA
UNDER
CRC
OVER
AB.IF
TIME
DATA
UNDER
F.E.(R.E.)
*1
CRC
OVER
AB.IF
TIME
DATA
UNDER
Network No. setting switch —
*3
NETWORK NO.
100, 10, 1
NETWORK NO.
100, 10, 1
Group No. setting switch —
*3
GROUP NO. GR.NO.
Station number setting switch
STATION NO.
10, 1
STATION NO.
10, 1
ST.NO.
10, 1
Mode setting switch
MODE
0: Online
*3
(parameters are valid)
1: Self-loopback test
2: Internal self-loopback
test
3: Hardware test
4: Online
*4
5: Self-loopback test
*4
6: Internal self-loopback
test
*4
7: Hardware test
*4
8 and up: Use rohibited
MODE
0: Online
1: Use prohibited
2: Offline (disconnected)
3: Forward loop test
4: Reverse loop test
5: Station-to-station test (master station)
6: Station-to-station test (slave station)
7: Self-loopback test
8: Internal self-loopback test
9: Hardware test
D: Network No. confirmation
E: Group No. confirmation
F: Station number confirmation
MODE
0: Online
1: Use prohibited
2: Offline (disconnected)
3: Forward loop test
4: Reverse loop test
5: Station-to-station test (master station)
6: Station-to-station test (slave station)
7: Self-loopback test
8: Internal self-loopback test
9: Hardware test
Display select switch — — DISPLAY L R
Condition setting switch —
*3
SW1 : PC
REMOTE
SW2 : N.ST
MNG
SW3 : PRM
D.PRM
SW4,5 : STATION SIZE
SW6,7 : LB/LW SIZE
SW1 : PC
REM
SW2 : N.ST
MNG
SW3 : PRM
D.PRM
SW4,5 : ST.SIZE
SW6,7 : LB/LW SIZE
Applicable CPU QCPU Q4ARCPU,QnACPU,Q2ASCPU Q2ASCPU
Applicable base Q3 B,Q6 B
A3
B,A5 B,A6 B,
A38HB,A37RHB,A3
RB,A68RB
A1S3
B,A1S5 B,
A1S6
B,A1S38HB
External dimensions
H
W D(mm(in.)) 98(3.86) 27.4(1.08)
90(3.54)
AJ71QLP21:
250(9.84)
37.5(1.48) 111(4.37)
AJ71QBR11:
250(9.84)
37.5(1.48) 113(4.45)
A1SJ71QLP21:
130(5.12)
34.5(1.36) 93.6(3.69)
A1SJ71QBR11:
130(5.12)
34.5(1.36) 104.6(4.12)
Weight (kg) 0.11 0.45 0.3
*1: The LED display is activated with the display selection switch.
*2: The detailed contents of an error code can be checked by the network diagnostics.
*3: Set with a network parameter.
*4: Only possible with the QJ71LP21-25. Use with the QJ71LP21 and QJ71BR11 is prohibited.