Specifications

6 - 7
(b) ZNWR
(Network No. designation)
J.ZNWR
J: Executed
when on
Write command
JP.ZNWR
JP: Executed
at startup
Write command
Jn n1 n2
Jn n1 n2
(D1) (S1) (D2)
(D1) (S1) (D2)
Setting details Setting range
Jn Network No. where the target station exists 1 to 239
n1 Target station number
1 to 64 (Constant)
81
H to A0H : Group designation
FF
H : Target network No, for
all stations
Designation of the number of digits
for bit device *
2
Word device *
3
(D1) Head device of the target station from which data is written T,C,D,W
(S1) Head device of the host that stores the data to be written Word device *
3
n2 Number of points to be written (word)
1 to 230 (Constant)
Designation of the number of digits
for bit device *
2
Word device *
3
(D2)
Completion device
Designate the host's device to be turned on for one scan upon
write completion
(D2)............. OFF: Not completed ON: Complete
(D2) + 1 ...... OFF: Normal ON: Abnormal
Bit device *
1
Bit designation of word device *
4
*1: Bit device : X, Y, M, L, F, V, and B
*2: Designation of the number of digits for bit device : Number of digits of K, bit device
head No.
*3: Word device : T, C, D, W, ST, R, and ZR
*4: Bit designation of word device : Word device, bit number