Specifications

5 - 16
5.4.2 Remote I/O station parameter settings
The following parameters are set for the remote I/O station as needed and are written to
the remote I/O module.
Prameters for the remote I/O station are shown below.
However, the remote I/O station can operate with the default settings of the remote I/O
module, so writing the parameters to the remote I/O module is not needed in
Assignment III.
(1) PLC parameter
In the remote I/O module, the PLC parameters similar to those set in the CPU
module can be set. Note that only necessary items for a remote I/O station can be
set.
Setting Item Sub-item Default
Points occupied by empty slot Points occupied by empty slot 16 Points
PLC system
Module synchronization
Synchronizes intelligent module's
pulse up
Synchronizes
Carries out fuse blown check Checks
PLC RAS Error check
Carries out I/O module comparison Checks
Remote I/O switch setting Remote I/O switch setting ——
Points/Start
Assignment method
Start/End
Start/End
Dev. name
Points/Start
Operational
settings
Forwarding parameter between
devices
Start/End
No setting
Type
Model name
Points
I/O Assignment
Start XY
No setting
Base model name
Power model name
Extension cable
Slots
I/O assignment
Standard setting
Base mode
No setting
Refer to the QCPU (Q Mode) User's Manual (Function Explanation. Program Fundamentals) for the
details about "PLC system", "PLC RAS", and "I/O assignment."
(2) Network parameters
In the remote I/O module, the network parameters similar to those set in the CPU
module can be set. Note that settable items are more limited than those on the CPU
module.
Setting Description
Ethernet settings Sets network parameters for the Ethernet module.
CC-Link settings Sets network parameters for the CC-Link module.