Specifications

5 - 14
POINT
(1) Set the input/output numbers loaded on the remote I/O station module for the
setting of the remote master station side.
Remote master station
Remote I/O station
0
1FFF
0
1FFF
Actual I/O
XY XY
If set shifted from the loaded condition, a malfunction will occur in the operation.
Remote master station
Remote I/O station
0
1FFF
0
1FFF
Actual I/O
XY XY
(2) It is possible to reduce the number of link points if the mounting is consolidated
into groups of input modules, intelligent function modules and output modules.
Power supply
Power supply
QJ72
LP25
Input module
Input module
Input module
Output module
Output module
Vacant
Vacant
Output module
XF
16
points
Input module
16
points
16
points
16
points
Output module
16
points
Output module
16
points
32
points
Input module
32
points
Input module
32
points
32
points
32
points
64
points
Output module
64
points
X2F Y5F YCFYBF
X/Y4F
X7F
Intelligent
function module
32
points
Intelligent
function module
Input assignment
range
Output assignment
range
X0 7F
Y30 CF
QJ72
LP25
XF X2F YCFYBF
X4F
Y7F
Input assignment
range
Output
assignment range
X0 6F
Y50 CF
X0 X10 X/Y30 Y50 X60 Y80 YC0 X0 X10 X30 X/Y50 Y70 Y80 YC0
X/Y6F
-25 -25