Specifications
5 - 12
(2) Parameter settings for remote I/O station
Set the following functions
as necessary.
Network parameter settings
1) Ethernet
2) CC-Link
WritingparameterstoremoteI/Omodule
Not
required
Required
To cable connection
PLC Parameters
1) PLC system settings
2) PLC RAS settings
3) Operational settings
4) I/O assignment
Set the following functions
as necessary.
Required
Not
required
Intelligent function module parameter settings
Resetting network module
POINT
1) If no parameters are written to the remote I/O station, the operation is performed
using the default settings.
2) If the CPU module for the remote master station is reset or set from STOP to RUN,
the remote I/O station is also reset.
3) Even if only one setting is corrected in the following modules, all the parameters
must be written to the remote I/O module: PLC parameters, intelligent function
module parameters, and network parameters.