User`s manual
3 - 3 3 - 3
MELSEC-Q
3 OUTPUT MODULE SPECIFICATIONS
3.3 QY22 TRIAC Output Module
TRIAC Output Module Type
Specifications
QY22 Appearance
Number of output points 16 points
Isolation method Photocoupler
Rated load voltage
100 to 240VDC 50/60Hz±5%
Load voltage distortion rate Within 5%
Maximum load voltage 264VAC
Maximum load current 0.6A/point, 4.8A/common
Minimum load voltage/current 24VAC 100mA, 100VAC 25mA, 240VAC 25mA
Maximum rush current 20A/cycle or less
Leakage current at OFF 3mA or lower (for 240V, 60Hz), 1.5mA or lower (for 120V, 60Hz)
Maximum voltage drop at ON 1.5V or lower
OFF to ON 1ms or less
Response time
ON to OFF 1ms + 0.5 cycles or less (rated load, resistance load)
Surge killer CR absorber
Fuse
None (Attaching a fuse to each external wiring is recommended. Refer to
Section 1.2 (16))
Dielectric maximum voltage 2830VAC rms/3 cycles (altitude 2000m)
Insulation resistance 10M or higher by insulation resistance meter
By noise simulator of 1.5kVp-p noise voltage,
1
s noise width and 25 to 60Hz noise frequency
Noise immunity
First transient noise IEC61000-4-4: 1kV
Protection of degree IP1X
Common terminal arrangement 16 points/common (common terminal: TB17)
Number of I/O points 16 (I/O allocation is set as a 16-points output module)
Operation indicator ON indication (LED)
External connections 18-point terminal block (M3 6 screws)
Applicable wire size
Core cable: 0.3 to 0.75mm
2
(Outside diameter: 2.8mm or smaller)
Applicable connector terminal R1.25-3 (Terminals with sleeve cannot be used)
5VDC internal current
consumption
250mA (Max., all points ON)
Weight 0.40kg
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
COM
QY22
100VAC
240VAC
0.6A
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
01234567
8 9 ABCDEF
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
External Connections Terminal Block Number Signal Name
TB1 Y00
TB2 Y01
TB3 Y02
TB4 Y03
TB5 Y04
TB6 Y05
TB7 Y06
TB8 Y07
TB9 Y08
TB10 Y09
TB11 Y0A
TB12 Y0B
TB13 Y0C
TB14 Y0D
TB15 Y0E
TB16 Y0F
TB17 COM
L
L
TB1
TB17
TB16LED
Internal
circuit
LED
100 to 240VAC
TB18 Vacant
1: Wire the module taking care so that the wiring does not interfere with the left-side module.