User`s manual
1 - 7 1 - 7
MELSEC-Q
1 GENERAL SPECIFICATIONS OF INPUT AND OUTPUT MODULES AND
INSTRUCTIONS FOR SELECTING THEM
(13)When confirming the product information on the CPU PLC, observe the system
monitor in the DIAGNOSIS menu of the GX Developer.
Confirm by
observing here.
(14)When using the QH42P, QX41Y41P or QX48Y57, configure it with the following
devices.
Part name Detail
CPU PLC Product of product information [011120000000000-A] or later
GX Developer
SW5D5C-GPPW or later
The CPU PLCs other than those listed above cannot be used.
When the SW4D5C-GPPW is used, the response time cannot be set
(fixed at 10ms).
Set OUTPUT for the I/O allocation.
(15)Possible constructions for QI60 compatible time settings
When setting compatible times for QI60, use the constructions listed below.
If using other constructions, compatible times can not be set. (Fixed at 0.2 ms)
Product name Contents
PLC CPU Product information "021120000000000-B" or later
GX Developer SW6D5C-GPPW or later