When reusing existing modules with a Q Series CPU, it is not required to change the I/O number of the existing
modules. For new module(s) on the main base unit, assign a number after the existing modules in the I/O assignment
settings. This can greatly reduce the program modification time.
●Remove the AnS/QnA extension base unit
(QA1S□B) when all modules have been replaced
with Q Series equivalents.
Existing AnS/QnAS Series
Step 1
■Gradual transition from Ans/QnAS Series to Q Series (Q mode).
●Construct a system that is controlled by the new Q Series CPU (Q mode) while keeping the existing AnS/QnAS
Series modules mounted to a QA1S□B extension base unit. The AnS/QnAS Series modules can gradually be
replaced to fully establish a Q Series system.
●The QA1S□B extension base units are compatible with High Performance Model QCPUs and Universal Model QCPUs
whose first five-digit serial number is 13102 or later. Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety
CPUs and Remote I/O Stations are not compatible.
●Some modules cannot be mounted on the QA1S□B extension base units. For details, see the "QCPU User's Manual
(Hardware Design, Maintenance and Inspection) (SH(NA)-080473ENG)".
●No further extensions can be made to QA1S51B as it has not got an Extension Cable Connector.
This unit cannot be used in conjunction with QA6□B and QA6ADP with A5□B nor can QA6ADP be used in
conjunction with A6□B.
QA1S65B
QA1S68B
QA1S51B
Q Series
Entire replacement
to Q Series
Step 2
Q Series
Q Series
extension
cable
Existing AnS/QnAS Series power
supply modules, I/O modules, and other
modules can be utilized; wiring is left as
it is.
■Reduce conversion effort by using the same I/O addressing.
Use existing AnS/QnAS Series modules
when upgrading to QCPU.
For AnS/QnAS Series
QA Extension Base Unit ( )
Replaced
modules
(AnS/QnAS to Q Series)
QA1S□B extension base unit
Q35B
0
0 1 2 3 4
1 2 3 4
5 6 7 8 9
Newly added
modules
A1SHCPU
A1SX41
A1SY41P
Q00UCPU
QJ61BT11N
QJ71LP21-25
QX41
A1SX41
A1SY41P
Empty
Empty
A1SX41
QX41
QY41P
A1SJ61BT11
A1SJ71LP21
A1SX41
Replace modules which cannot be mounted with Q Series modules.
Note: Assign the I/O numbers in the following order: Q Series to AnS/QnAS Series or AnS/QnAS Series to Q Series.
When the order is mixed (i.e., Q Series → AnS/QnAS Series → Q Series), an error will occur in the CPU.
■Example of I/O assignment
TypeModel
0
1
2
3
4
Intelli.
Intelli.
Input
Input
Output
A1SX41
A1SY41P
A1SX41
QJ61BT11N
QJ71LP21-25
QX41
QX41
QY41P
100
120
140
160
180
5
6
7
8
9
Input
Output
Empty
Empty
Input
32
32
32
32
32
00
20
40
60
80
Address TypeModel Point Address
Main base unit
Extension base unit
32
32
32
32
32
Point
QA Extension
Base Unit
QA1S65B
QA1S68B
QA1S51B