Technical information

57
MITSUBISHI ELECTRIC
MICRO CONTROLLERS
MICRO CONTROLLERS ///
CC-Link Master and Slave Modules
The CC-Link network enables the controlling
and monitoring of decentralized I/O modules at
the machine.
The CC-Link master module FX2N-16CCL-M is a
special ex tension block which assigns an FX
series PLC as the master station of the CC-Link
system.
The setting of all modules within the network is
handled direc tly via the master module.
Up to 15 remote stations and remote device
stations can be connected to the master station
as decentralized I/O stations. These remote sta-
tions can be up to 7 I/O modules and up to 8
intelligent module s. 2 master module s can be
connected to one FX
1N or FX2N base unit.
The maximum communications distance is
1200 m without repeater.
The communication module FX
2N-32CCL
enables the user to connect the F X PLC as a
slaveonanexistentCC-Linknetwork.
The buffer memory of the FX
2N-32CCL is read
and written by FROM/TO instructions.
The FX2N- 32CCL can be used by FX1N/FX2N
and FX3U/FX3UC PLCs.
The connection is to the extension bus on the
right-hand-side of the controller.
Specifications FX2N-16CCL-M FX2N-32CCL
Module type Master station Remote station
Link points per station
I/O points 32 32
register 8 8
Max. number of I/O points
128 (with FX1N PLC), 256 (with FX2NPLC),
384 (with FX3U PLC)*
Number of connectable modules Max. 15
Power supply
5 V DC Max. 130 mA (from base unit)
24 V DC 150 mA 50 mA
Related I/O points 8 8
Dimensions(WxHxD) 85x90x87 43x90x87
Order information
Art. no. 133596 102961
Note: Refer to the Network section of this catalog for I/O blocks and power supply units.
*Including I/O points in PLC and network.
FX -16CCL-M
2n
CC-
LINK
RUN
ERR.
MST
TEST 1
TEST 2
L RUN
L ERR.
SW
M/S
PRM
TIME
LINE
SD
RD
LRUN•LERR•RD•SD
FX -32CCL
2N
Network Module for CANopen
The FX2N-32C AN communications module
makesitpossibletoconnectanFX
1N,FX2N or
FX3U/FX3UC PLC to an existing CANopen net-
work.
In addition to real-time capabilities and
high-speed data transfer at rates of up to
1Mbit/s the CANopen module also has high
transfer reliability and simple network
configuration. Up to 120 data words can be sent
and received as process data objects (30 PDOs).
The number of words that can be transmitted in
each direction can be set between 1 and 120.
Communication with the module’s memory
buffer is performed with simple FROM/TO
instructions.
Specifications FX2N-32CAN
Module type CANopen master
CAN standard ISO 11898/1993
CANopen standard byCiA DS-301 version 3.0
Additional CANopen features
NMT, Guarding, and Guarding request based on DS-302 V2.0.
network variables basedon DS-405V1.0
Max. nbr. of modules that can be con
-
nected to the network
30 without repeater; 127 with repeater
Station numbers 1 127
Supported baud rate kBaud 10, 20, 50, 125, 250, 500, 800, 1000
Power supply
5 V DC 290 mA
24 V DC
Related I/O points 8
Dimensions(WxHxD) mm 43x90x88.7
Order information
Art. no. 141179
FX -32CAN
2N
POWER
RUN
FROM/TO
Tx/Rx
ERROR
Automation Book_UK_2008.prn
Automation Book_UK_2008
Dienstag, 8. April 2008 18:21:04
Farbprofil: Deaktiviert
Komposit Standardbildschirm