Technical information
20
MITSUBISHI ELECTRIC
NETWORKS
/// NETWORKS
Specifications ST1H-PB
Occupied I/O points 4 / 4
Communications
protocol IEC 61158/EN50170
medium Shielded 2-wire
Interface type RS485
Supported operation modes Sync mode, freeze mode
Max. transmission distance m 4800(3 repeaters)
Programming interface RS232 Mini-DIN socket for diagnostics and programming
Data exchange with master 304 total / 32 / 64 / 128 / 256, selectable mode
Number of addressable slices max. 63
Addressable I/O points
digital bit 256
analog word 32
Internal power consumption(5 VDC) mA 530
External power supply Via ST1PSD
Dimensions (W x Hx D) mm 114.5 x 50.5 x 74.5
Order information
Art. no. 152951
Basic module (head station) of the
MELSEC ST series
The basic module ST1H-PB connec ts the
remote I/O modules of the ST series to
PROFIBUS/DP.
The ST1H-PB provides a Mini-DIN socket
for diagnostics and parameter setting.
The station number can be set via DIP
switches on the basic module. LEDs
show the status ofthe connected systems.
Bus power for head station
The Bus power supply and refresh mod-
ule ST1PSD can serve in two ways: dis-
tribute 24 V DC power supply for the
basic module and I/O devices plus
5 V DC for the internal backplane bus
(H mode) or distribute 24 V DC power
supply for I/O devices and refresh the
internal backplane b us with 5 V DC
(R mode). Each mode (H or R) is indi-
cated by the use of a different base mod-
ule, marked with "H" or "R".
You need 1 ST1PSD with H -type base
module beside the basic module to
operate the ST station, a second or more
(usingtheR-typebasemodule)areonly
needed depending on the power con-
sumption of the c onnec ted items ( see
bottom of this p age).
LEDs on the module show the s tatus for
RUN and ERROR. Diagnosis can be made
via the head module.
Power feeding module
The power feeding module ST1PDD dis-
tributes 24V DC only for the I/Os of the
actuators and sensors.
The number of ST1PDD modules needed
can b e calculated individually b y addi-
tion of the current consumption of all
connected devices.
The electronic module is fitted in a base
module, which can be installe d on a
standard DIN rail.
Specifications ST1PSD ST1PDD
Module type
Power supply for head station,internal 5V DC backplane bus and 24V DC for I/Os (double
function)
Power feeding module
Occupied I/O points 2 / 2 2 / 2
Occupied slice number 2 1
Nominal voltage V DC 24.0 24.0
Permissible range 24.0 (19.2 – 28.8 (±20%)) 24.0 (19.2 – 28.8 (±20%))
System supply V DC 24.0for basicmodule and I/O´s, field supply / 5.0 for internalbackplanebus
Ripple < 5 % < 5 %
Internal power consumption(5 VDC) mA 60
Max. output current (5V DC) A 2.0 —
Max.outputcurrent(24VDC) A 8(10withfuse) 8 (10withfuse)
Dimensions (W x Hx D) mm 25.2 x 55.4 x 74.1 12.6 x 55.4 x 74.1
Order information
Art. no. 152952 152953
Applicablebase module for
basic module supply
spring clamp type ST1B-S4P2-H-SET, art. no. 152908 ST1B-S4P2-D, art. no. 152910
screw clamp type ST1B-E4P2-H-SET, art. no. 152918 ST1B-E4P2-D, art. no.152920
Applicablebase module for
bus refreshing withinthe
station
spring clamp type ST1B-S4P2-R-SET, art. no. 152909 —
screw clamp type ST1B-E4P2-R-SET, art. no.152919 —
Note: Calculation of the power consumption
ThepowerconsumptionandtheneedofapowerrefreshmodulewillbecalculatedexactlyintheGXConfiguratorDP
during your configuration of the System.
For a rough calculation of the internal 5V DC power consumtion and a rough calculation for the number of needed PSD
refresh modules, please refer to the attached table.
Module type Power supply/consumtion Description
ST1PSD 2.0A Power supply infeed
ST1H-PB 0.53A Power consumption
Slicemodule 0.1A Powerconsumption
Blockmodule 0.15A Power consumption
RELEASE
+
-
MITSUBISHI
STATION
ST1H-PB
S
T
A
T
I
O
N
N
O.
80
RUN
M1
RS-232C
PROFIBUS I/F
RESET
M0
SYN.
FRE.
ERR.
REL.
DIA
BF
8
40
4
20
2
10
1
The MELSEC ST Series for PROFIBUS/DP
11
12
13
14
22
23
24
ST1PSD
RUN
ERR.
PW
32
33
34
42
43
44
ST1PDD
RUN
ERR.
PW
11
12
13
14
22
23
24
Automation Book_UK_2008.prn
Automation Book_UK_2008
Dienstag, 8. April 2008 18:16:38
Farbprofil: Deaktiviert
Komposit Standardbildschirm