11. ERROR CODES STORED AT THE PCPU
11 14
Table 11.3 Servo Amplifier Error List (2000 to 2799) (Continued)
Error Cause
Error
Code
Amplifier
Type
Name Description
When Error Checked Error Processing Corrective Action
The servo motor connected is not
as set.
Reconsider the system settings.
The U, V, and W phases of the
ADU output resulted in a short
circuit or ground fault.
Check the servo motor cable.
Wiring mistake of the U, V, and W
phases of the ADU output.
Correct the servo motor wiring.
Damage to the ADU's transistor
module.
ADU fault.
Change the ADU.
Coupling fault of servo motor and
encoder.
Change the servo motor.
A
The servo motor oscillated.
At power-on of servo
amplifier
At servo error reset
Reconsider the servo parameters.
U, V, W in the servo amplifier
outputs have short circuited with
each other.
Check if there is a short circuit between
U, V, W of the servo amplifier outputs.
U, V, W in the servo amplifier
outputs have shorted to ground.
Check if U, V, W of the servo amplifier
outputs have been grounded to the
ground terminal. Check if U, V, W of
the servomotor are grounded to the
core.
If grounding is found, replace the servo
amplifier and/or motor.
Incorrect wiring of U, V, W phases
in the servo amplifier outputs.
Correct the wiring.
The servo amplifier transistor is
damaged.
Replace the servo amplifier.
Failure of coupling between
servomotor and encoder
Replace the servomotor.
Encoder cable failure
Replace the encoder cable.
A servomotor that does not match
the setting has been connected.
Check the connected motor set in the
system settings.
The servomotor oscillated.
Check and adjust the gain value set in
the servo parameters.
2032
M
Overcurrent
Noise entered the overcurrent
detection circuit.
Check if any relays or valves are
operating in the vicinity.
The converter bus voltage has
reached 400 V or more. (800VAC
or more for 400VAC series servo)
The frequency of acceleration and
deceleration was too high for the
regenerative ability.
The regenerative resistor has been
connected incorrectly.
Increase the acceleration time and
deceleration time in the fixed
parameters.
Check the connection between C and P
of the terminal block for the terminal
block for regenerative resistance.
The regenerative resistor in the
servo amplifier is destroyed.
Measure between C and P of the
terminal block for regenerative
resistance with a multimeter; if
abnormal, replace the servo amplifier.
(Measure about 3 minutes after the
charge lamp has gone out.)
The power transistor for
regeneration is damaged.
Replace the servo amplifier.
2033
M
Overvoltage
The power supply voltage is too
high.
Measure the input voltage (R, S, T) with
a voltmeter.
2034
M
Communications
error
Error in data received from the
servo system CPU
At any time during operation
Immediate stop
Check the connection of the motion bus
cable.
Check if there is a disconnection in the
motion us cable.
Check if the motion bus cable is
clamped correctly.