Instruction manual
8. OUTPUT MODULES
8 − 55
(g) FLS signal (M2411+20n)
1) The FLS signal is controlled according to the ON/OFF status of upper
limit switch inputs (FLS) to the A278LX or A172SENC from an external
source.
• Upper limit switch input OFF ......... FLS signal ON
• Upper limit switch input ON........... FLS signal OFF
2) The upper limit switch (FLS) status at FLS signal ON/OFF is shown
below.
When FLS signal is ON When FLS signal is OFF
A278LX/A172SENC
FLS
FLS
COM
A278LX/A172SENC
FLS
FLS
COM
(h) RLS Signal (M2412+20n)
1) The RLS signal is controlled according to the ON/OFF status of lower
limit switch inputs (RLS) to the A278LX or A172SENC from an external
source.
• Lower limit switch input OFF ........ RLS signal ON
• Lower limit switch input ON.......... RLS signal OFF
2) The lower limit switch (RLS) status at RLS signal ON/OFF is shown
below.
When RLS signal is ON When RLS signal is OFF
A278LX/A172SENC
RLS
RLS
COM
A278LX/A172SENC
RLS
RLS
COM
(i) STOP signal (M2413+20n)
1) The STOP signal is controlled according to the ON/OFF status of STOP
signal inputs to the A278LX or A172SENC from an external source.
• STOP signal OFF.........STOP signal OFF
• STOP signal ON...........STOP signal ON
2) The STOP signal status at STOP signal ON/OFF is shown below.
When STOP signal is ON When STOP signal is OFF
STOP
COM
A278LX/A172SENC
STOP
A278LX/A172SENC
STOP
STOP
COM