Configuration with the Configuration Tool
28 Mitsubishi Electric, MA00759F
Updating Drivers from Disk
Select File/Update Drivers From/Disk to update available drivers to the latest ver-
sion, or to install new drivers from disk. Browse to the folder where the driver files
are is located. A list of all drivers that can be installed is now shown. Then follow the
instructions above.
3.6 Changing Project Properties
Both the selected operator panel and controller can be changed for the project.
Double-click on the project name in the Project Manager to display the Project Prop-
erties dialog. Click Change for the parameter Operator Terminal and/or Controller
systems.
Changing Operator Panel Version
If the system program in the operator panel is updated to a newer version, the oper-
ator panel version in the Project Properties dialog has to be changed also. Otherwise,
the new functionality in the new operator panel version cannot be utilized.
Changing Controller
If the controller in the project is changed to a system with another name for the
signals used, these must be changed. This is easily done by using the internal name
list. See the section The Name List.
1. Select View/Name List.
2. Click on the button Undefined to insert all I/Os used in the project in the name
list.
3. Click on the button Export to export the name list to a text file. Enter a name
and click Save. Define how the text file is to be separated.
4. Open the text file in a text editor, e.g. Wordpad.
5. Change all I/Os to signals used in the new controller, and save the file as a text
file.
6. Double-click on the project name in the Project Manager to display the Project
Properties dialog. Click Change for Controller.
7. Select the new controller to be used and click OK twice.
8. Click on the button Import in the dialog Name list, and click No to the
question if invalid I/Os should be removed.
9. Click on the Rebind button to update all new I/Os in the project with the new
names.