Network Communication
254 Mitsubishi Electric, MA00759F
The transfer must be handled as follows:
1. The handshake register must be 0. If not, reset the command register to 0.
2. Enter the command in the command register.
3. Wait for the ready signal or error code in the handshake register.
4. Set the command register 0. The operator panel will now set the handshake
register to 0.
Synchronize clock with server
Indicate if the client clock is to be synchronized with a selected server (operator pan-
el). The server is selected by giving the number of the server in the entry field. If the
clock in the client is changed locally, the change will also be transferred to the selected
server.
BDTP server address
Under BDTP Server Address, indicate the IP addresses to the servers from which the
client will be able to retrieve data. The addresses will be indexed in the order they are
entered.
When objects are programmed in the project you must indicate from which server
the address is to be taken. In the address field in the object dialogs, you specify the
following:
server index>device
If, for example, 2>D15 is indicated in the address field, the value for the object will
be collected from register D15 in the server with index 2.
It is possible to change the server index in a client program with the function BDTP
Station change. See the section Changing BDTP Station.
Note:
If there is no controller connected to the BDTP Client (the operator panel,) the units
Controller 1 and Controller 2 must be moved from RS-232C/RS-422/RS-485 to
Unused functions in the Peripheral configuration dialog.