Configuration with the Configuration Tool
Mitsubishi Electric, MA00759F 25
Internal Variables
Internal variables can be used and selected in the same way as different drivers. A
number of volatile and non-volatile user-defined variables can be selected. When a
value is changed, the non-volatile variables are saved in the flash memory to be read
at the next start-up. The system variables are fixed. These can be used to display e.g.
poll intervals and for toggle functions. By clicking Properties & Help in the I/O
Browser or selecting Functions /I/O Configuration/Internal Variables the following
window is displayed.
The system variables are used according to the tables below:
Variable type Addressing area, bit Addressing area, memory cell
Volatile M0 - M4095 D0 - D4095
Non-volatile M4096 - M8191 D4096 - D8191
System M8192 - M8199 D8192 - D8199
Bit Description
M8192 Always ON
M8193 Toggles between OFF and ON every second
M8194 Toggles between OFF and ON every 500 ms
M8195 Toggles between OFF and ON every 200 ms