User`s guide

Table Of Contents
Passwords
Mitsubishi Electric, MA00759F 187
11.3 Logging in
If the box for automatic login in the Password dialog is not checked, the login will
either be controlled from a function or touch key, or through a digital signal from the
controller (Login signal). If the function key linked to the function Login to
specified security level is pressed, or the digital signal is activated, the input field for
login will be shown. Specify password. The password is linked to a security level, see
above.
11.4 Password for Project Transfer
Commands can be entered on the command line by double-clicking on System
Signals in the Setup folder in the Project Manager. By entering the command
PDxxxxxxxx, where xxxxxxxx represents the password, this password must be given
to access the functions in the TRANSFER menu in the operator panel. When trans-
ferring projects from the configuration tool to the operator panel this password must
be given in the operator panel. Only capital letters can be used on the command line.
Logout signal A signal which, when it is set to one, logs out the current user. The
function can also be linked to a function or touch key. See the
chapter Function Keys for further information.
Login level reg. A register in the controller to control the security level can be
specified here. The value in the register determines the current
security level, value 0 = no security level, 1 = security level 1, etc.
Current level
reg.
Specify a register from where the operator panel can present the
current security level (0-8).
Login timeout Specify the time in minutes which the operator panel can remain
inactive before the user is automatically logged out. If 0 is given
there will be no logout.
Password RUN/
PROG
This function is not used for the E1000 operator panels.
Automatic
login
Specify if the login window is to be automatically shown when trying
to access password-protected blocks or keys. For touch screen
operator panels, the function is also applicable for objects.
Parameter Description