Data Logger
184 Mitsubishi Electric, MA00759F
For information about Data Logger backup and transfer, please see the respective
section in chapter Tre nd s.
Sample full limit State by which number of samples Sample full signal is to be set,
and which signal to set.
Sample full signal
Store Select Changed to store only values that are different from the
last sampling.
Select All to store all values.
Enable sampling
signal
State a digital signal that, when set, starts logging data. The log-
ging is stopped if the signal is reset. The parameter is optional.
Erase samples
signal
State a digital signal that, when set, erases logged data.
The parameter is optional.