User`s guide

Table Of Contents
Alarm Management
168 Mitsubishi Electric, MA00759F
8.8 Graphic Alarm Page
This page is graphic and the pre-defined function keys or touch keys can be modified
by the user. The alarm list area of the page cannot be modified by the user. Function
keys or touch keys are linked to functions to enlarge or reduce the text on the alarm
page, including page browsing functions. There is also a function to select whether
the date and time stamps are to be shown. Alarms can be sorted by group, and the
group shown is optional. Status is shown with different colors, i.e. the colors defined
when setting the alarm groups.
The command ALOFx can be used to indicate if any active alarms are deleted from
the alarm list (alarm list overflow). Select Setup/System Signals and then type ALOF
followed by a bit device (x) on the Commands line. If an active alarm is deleted, the
bit will be set.
Note:
The graphic alarm page (alarm list) is printed as a text printout.
Switch on/off date
and time stamps
Alarm status symbol
Alarm text
Zoom
Acknowledge
Scroll one page up
Display Alarm info
Scroll one page down
Alarm repeat counter
block
User-defined alarm groups
Scroll button for alarm groups Scroll button for alarm groups
Return to previous
block