Installation manual
Table Of Contents
- Foreword
- 1 Safety Precautions
- 2 Installation
- 2.1 Space Requirements
- 2.2 Installation Process
- 1. Unpack and check the delivery. If damage is found, notify the supplier.
- 2. Place the panel cut out where the operator terminal is to be situated, draw along the outer sides of the holes and cut according to the markings.
- 3. Secure the operator terminal in position, using all the fastening holes and the provided brackets and screws:
- 4. Connect the cables in the specified order.
- 5. Carefully remove the laminated film over the operator terminal display, to avoid static electricity that could damage the terminal.
- 2.2.1 Mode Switches
- 2.2.2 Connections to the Controller
- 2.2.3 Other Connections and Peripherals
- 3 Technical Data
- 4 Chemical Resistance
- 5 Operator Terminal Drawings

Installation
Mitsubishi Electric, MA00779 2-1
2 Installation
2.1 Space Requirements
– Installation plate thickness: 1.5 - 9.0 mm (0.06 - 0.35 inch)
– Space requirements when installing the operator terminal:
Caution
The openings on the enclosure are for air convection. Do not cover these openings.
2.2 Installation Process
1. Unpack and check the delivery. If damage is found, notify the supplier.
Note:
Place the operator terminal on a stable surface during installation.
Dropping it or letting it fall may cause damage.
2. Place the panel cut out where the operator terminal is to be situated, draw along
the outer sides of the holes and cut according to the markings.
58 mm
228 mm
302 mm
100 mm
(4.0 inch)
100 mm
(4.0 inch)
50 mm
(2.0 inch)
50 mm
(2.0 inch)
100 mm
(4.0 inch)
(2.28 inch)
(11.89 inch)
(8.98 inch)
x13
Panel cut out 264.5 x 206.0 mm
(10.41 x 8.11 inch)