Specifications
App - 47
1) Connect the GX Developer and Ethernet module to
the Ethernet.
2) Click the [Online]
[Transfer setup] menu.
3) Select "Ethernet" of the PC side I/F, and make the
setting for the following items.
Network No. : 1
Station No. : Station No. of each personal
computer (1 to 5)
Protocol : TCP
Continued to the next page
4) Select "Ethernet module" of the PLC side I/F, and
make the settings for the following contents.
Computer type : QJ71E71
Network No. : 1
Station No. : Station No. of each
demonstration machine (11 to
15)
IP address/Host : Set IP address of each
demonstration
machine(192.168.1.101 to
192.168.1.105)
Routing parameter transfer method:
Automatic transfer method
(Automatic response system)