Error code Description of error Corrective action
0x01808009
COM port handle error
The handle of COM port cannot be
acquired.
The COM port object cannot be
copied.
The SOCKET object cannot be
copied.
Confirm that there is no application using the COM port.
Complete a program and restart the DOS/V personal computer.
0x0180800A
Buffer size setting error
The buffer size setting of the COM
port has failed.
Confirm that there is no application using the COM port.
Set the COM port in the control panel of the OS.
Complete a program and restart the DOS/V personal computer.
0x0180800B
DCB value acquisition error
Acquiring the DCB value of the COM
port has failed.
Confirm that there is no application using the COM port.
Set the COM port in the control panel of the OS.
Complete a program and restart the DOS/V personal computer.
0x0180800C
DCB setting error
Setting the DCB value of COM port
has failed.
Confirm that there is no application using the COM port.
Set the COM port in the control panel of the OS.
Complete a program and restart the DOS/V personal computer.
0x0180800E
Shared memory open error
The open processing of the shared
memory has failed.
Confirm that the GX simulator is started.
Complete a program and restart the DOS/V personal computer.
0x0180800D
Timeout value setting error
Setting the timeout value of the
COM port has failed.
Review the timeout value of property.
Review the timeout value in the communication setting utility.
Confirm that there is no application using the COM port.
Set the COM port in the control panel of the OS.
Complete a program and restart the DOS/V personal computer.
0x01808101 Double close error Complete a program and restart the DOS/V personal computer.
0x01808102
Handle close error
The handle close of the COM port
has failed.
Complete a program and restart the DOS/V personal computer.
0x01808103
Driver close error
The handle close of the driver has
failed.
Complete a program and restart the DOS/V personal computer.
0x01808201
Send error
Sending a data has failed.
Review the systems such as the PLC CPU, module setting and
cable status.
Set the COM port in the control panel of the OS.
Set the Ethernet board and protocol in the control panel of the OS.
Complete a program and restart the DOS/V personal computer.
0x01808202
Send data size error
Sending a data has failed.
Complete a program and restart the DOS/V personal computer.
0x01808203
Queue clear error
The queue clear of the COM port
has failed.
Complete a program and restart the DOS/V personal computer.
Execute the Close, then execute the Open again
0x01808301
Receive error
Receiving a data has failed.
Review the systems such as the PLC CPU, module setting and
cable status.
Review the timeout value of the property.
Review the timeout value in the communication setting utility.
Complete a program and restart the DOS/V personal computer.