Specifications
App - 38
Error code Description of error Corrective action
0x01802016
Station No. designation error
The method does not support the
operation for the designated station
No.
Review the station No.
0x0180201C
Write clock data error
As the designated write clock data is
error, the data cannot be correctly
written.
Review the write clock data.
0x0180201D
Write clock data error during RUN
Writing the clock data has failed.
For the PLC CPU being RUN, the
clock data cannot be written.
Change the PLC CPU to the STOP status.
0x01802020
Starting I/O No. error
The starting I/O No. designated in a
method is unauthorized.
Check the starting I/O No. designated in the method.
Check the PLC CPU parameter (I/O assignment) with the GPP
function.
Complete a program and restart the DOS/V personal computer.
0x01802021
Starting address error
The buffer address designated in a
method is unauthorized.
Check the buffer address value designated in the method.
Complete a program and restart the DOS/V personal computer.
0x01802038
Clock data read/write error
The clock data read/write method is
executed for the PLC CPU without
the clock element.
Do not execute the clock data read/write.
0x01808001 Double open error Complete a program and restart the DOS/V personal computer.
0x01808002
Channel No. designation error
The port Nos. that has set a property
and is set in the communication
setting utility are unauthorized.
Set the correct value in the port No. of property.
Perform the communication setting in the communication setting
utility again.
0x01808003
Driver not started
The driver of network board is not
started.
Start the driver.
0x01808005
MUTEX generation error
MUTEX generation for exclusive
control has failed.
Complete a program and restart the DOS/V personal computer.
Reinstall the MX Component.
0x01808007
Socket object generation error
The generation of Socket object has
failed.
Confirm that the application using the same port No. is started.
Retry the generation after changing the port No. of property.
Retry the generation after changing the port No. in the
communication setting utility.
Set the Ethernet board and protocol in the control panel of OS.
Complete a program and restart the DOS/V personal computer.
0x01808008
Port connection error
Establishment of connection has
failed.
Communication target has not
responded.
Review the IP address and port No. of property.
Review the port No. in the communication setting utility.
Review the systems such as the PLC CPU, module setting and
cable status.
Complete a program and restart the DOS/V personal computer.