Specifications

6 - 4
Continued from the previous page
4) Set the following contents of the Network
parameters Setting the number of MNET/10H
Ethernet cards screen.
Network type : Ethernet
I/O No. : 00A0
Network No. : 1
Group No. : 0
Station No. : Set the station No. of each
demonstration machine (11 to 15)
Mode : On line
5) Click the Operational settings
button to display
the Ethernet operations dialog box.
6) Set the following contents, click the End
button,
and then close the Ethernet operations dialog box.
Communication data code : ASCII code
Initial timing : Always wait for OPEN
IP address : Set the IP address of
each demonstration
machine
(192.168.1.101 to
192.168.1.105)
Send frame setting : Ethernet (V2.0)
7) Click the Open settings
button to display the
Network parameter Ethernet open settings screen.
Continued to the next page
8) Set the following contents.
Protocol : TCP
Open system : Active
Fixed buffer : Send
Fixed buffer communication procedure:
Procedure exist
Pairing open : Disable
Existence confirmation : No confirm
Host station Port No. : 0401
Transmission target device IP address:
Set the IP address of
each demonstration
machine (192.168.1.201
to 192.168.1.205)
Transmission target device Port No.:
0401