Specifications

WR2SD-6
WR2-SERIES SYSTEM DESIGN (June 2010)
WR2-SERIES
SYSTEM DESIGN
1. ELECTRICAL WORK
1-2-3. Electrical Characteristics of BC Controller
Symbols: MCA : Min.Circuit Amps (=1.25 x RLA)
RLA : Rated Load Amps
BC-Controller for PQRY-P-TGMU
Model Hz Volts Voltage range MCA(A) MOCP RLA(A)
CMB-P104NU-G
60Hz 208 / 230V 198 to 253V
0.36 / 0.34 15 / 15 0.29 / 0.27
CMB-P105NU-G 0.45 / 0.40 15 / 15 0.36 / 0.32
CMB-P106NU-G 0.53 / 0.48 15 / 15 0.42 / 0.38
CMB-P108NU-G 0.68 / 0.61 15 / 15 0.54 / 0.49
CMB-P1010NU-G 0.84 / 0.75 15 / 15 0.67 / 0.60
CMB-P1013NU-G 1.08 / 0.98 15 / 15 0.86 / 0.78
CMB-P1016NU-G 1.31 / 1.19 15 / 15 1.05 / 0.95
CMB-P108NU-GA 0.68 / 0.61 15 / 15 0.54 / 0.49
CMB-P1010NU-GA 0.84 / 0.75 15 / 15 0.67 / 0.60
CMB-P1013NU-GA 1.08 / 0.98 15 / 15 0.86 / 0.78
CMB-P1016NU-GA 1.31 / 1.19 15 / 15 1.05 / 0.95
CMB-P104NU-GB 0.33 / 0.30 15 / 15 0.26 / 0.24
CMB-P108NU-GB 0.64 / 0.59 15 / 15 0.51 / 0.47