Specifications
WR2-SERIES SYSTEM DESIGN (June 2010)
WR2SD-5
WR2-SERIES
SYSTEM DESIGN
1. ELECTRICAL WORK
1-2-2. Electrical Characteristics of Water-source Unit
Symbols: MCA : Min.Circuit Amps
SC : Starting Current RLA : Rated Load Amps
PQRY-P-T(S)HMU
Model Unit Combination
Water-source unit Compressor
Hz Volts Voltage range RLA(A) MCA(A) Max.Fuse(A) SC(A)
PQRY-P72THMU-A -
60Hz 208/230V 188 to 253V
12.6/11.4 16/15 25/20 15
PQRY-P96THMU-A - 18.0/16.2 23/21 40/30 15
PQRY-P120THMU-A - 23.6/21.4 30/27 50/40 15
PQRY-P144TSHMU-A
PQRY-P72THMU-A 12.6/11.4 16/15 25/20 15
PQRY-P72THMU-A 12.6/11.4 16/15 25/20 15
PQRY-P168TSHMU-A
PQRY-P72THMU-A 12.6/11.4 16/15 25/20 15
PQRY-P96THMU-A 18.0/16.2 23/21 40/30 15
PQRY-P192TSHMU-A
PQRY-P96THMU-A 18.0/16.2 23/21 40/30 15
PQRY-P96THMU-A 18.0/16.2 23/21 40/30 15
PQRY-P216TSHMU-A
PQRY-P96THMU-A 18.0/16.2 23/21 40/30 15
PQRY-P120THMU-A 23.6/21.4 30/27 50/40 15
PQRY-P240TSHMU-A
PQRY-P120THMU-A 23.6/21.4 30/27 50/40 15
PQRY-P120THMU-A 23.6/21.4 30/27 50/40 15
Symbols: MCA : Min.Circuit Amps
SC : Starting Current RLA : Rated Load Amps
PQRY-P-Y(S)HMU
Model
Unit Combination Heat source unit Compressor
Hz Volts Voltage range RLA(A) MCA(A) Max.Fuse(A) SC(A)
PQRY-P72YHMU-A -
60Hz 460V 414 to 506V
5.7 8 15 7
PQRY-P96YHMU-A - 8.1 11 15 7
PQRY-P120YHMU-A - 10.7 14 20 7
PQRY-P144YSHMU-A
PQRY-P72YHMU-A 5.7 8 15 7
PQRY-P72YHMU-A 5.7 8 15 7
PQRY-P168YSHMU-A
PQRY-P72YHMU-A 5.7 8 15 7
PQRY-P96YHMU-A 8.1 11 15 7
PQRY-P192YSHMU-A
PQRY-P96YHMU-A 8.1 11 15 7
PQRY-P96YHMU-A 8.1 11 15 7
PQRY-P216YSHMU-A
PQRY-P96YHMU-A 8.1 11 15 7
PQRY-P120YHMU-A 10.7 14 20 7
PQRY-P240YSHMU-A
PQRY-P120YHMU-A 10.7 14 20 7
PQRY-P120YHMU-A 10.7 14 20 7