Datasheet
LTX-VCI Datasheet
LTX-VCI Iss1.05
RealTime Control Systems Ltd. Park House, Greenhill Crescent, Watford WD18 8PH. Tel 01923 233384 Fax 01923 233385 Page 5
Web:
www.realtime-controls.co.uk
, E-mail:
support@realtime-controls.co.uk
LTX-VCI Datasheet Issue 1.05.01 12/07/2003 Doc No. 92101
Device Interface Sheet: Daikin L-Gateway DCS601A1R
Manufacturer Daikin
Device Name L-Gateway Prototype
Product Code DCS601A1R
Program ID 90:00:87:48:50:04:04:02
Indoor Units 64
VCI Mode Number 10
LTX-VCI compatibility v0.90 or greater
Interface Functionality
Control Function Comments
Setpoint
Range restrictions may be applied by LTX interfaces
Fanspeed
Only low or high speed available. Fanspeed settings of AUTO,
LOW and MEDIUM are treated as LOW, HIGH is treated as
HIGH
Run Mode
HEAT, COOL, AUTO and FAN_ONLY available
Louver
Not available on L-Gateway.
On/Off
Standard behaviour
Central/Local
Control
L-Gateway allows separate switching of On/Off, Setpoint and
Mode switches. The LTX-VCI will switch all as a single global
setting of Central or Local.
Readback Function Comments
Return air
temperature
Available in L-Gateway
Heat-exchanger
temperature
Not available
Fault Code
Selected Daikin fault codes are mapped into the LTX – see
fault code reference table
Setpoint
Setpoint readback will indicate the actual unit setpoint, this
may be offset by the unit from the demand setpoint
Fanspeed
Readback will return either LOW or HIGH
Run Mode
Run mode readback will indicate actual operating mode, during
AUTO operation readback will indicate actual mode (COOL,
HEAT etc)
Louver
Not available
On/Off
Standard
Additional Functions Comments
Fault Reset
Not Available
Filter Reset
Available if implemented on LTX BMS controller
Configuration Notes
No specific configuration requirements.