Technical information

Troubleshooting and Repair
65
3. You should get a reading of 1 Vac or less.
If your reading is greater than 1 Vac, check to see if your electrical panel
ground connects to the building ground. Depending on local utility
regulations, the connection usually exists between the electrical panel
ground and a cold water pipe entering the building. If this connection is
present, try an alternate ground point(s) and measure the AC voltage again.
If the system ground and safety ground both connect to the building
ground, your measurement is the metallic loop from the PBX chassis, to
the electrical panel ground, to the cold water pipe, and back through the
system ground wire.
If the safety ground and system ground do not connect at the electrical
panel, your measurement indicates the AC voltage differential between
protective earth and the building ground.
Ground Path Resistance Test
1. Turn off the main PBX system circuit breaker.
2. At the PBX system, connect the cabinet’s chassis ground to the
electrical panel ground. The wire should be a minimum 10 AWG and
not longer than 15 meters.
3. At the PBX system, disconnect the ground wire from the system’s
ground-stud.
4. Set your meter to OHMS at the highest scale.
5. Measure the resistance between the PBX chassis safety ground and
the ground wire that provides the system ground. Adjust your meter
down until you get a reading.
6. The resistance between the two grounds should be less than five
OHMS. If not, try alternate ground point(s) and repeat the test.
Testing the CO and PBX Ground Differential
If a PBX experiences trunk lock-ups, or trunk seize failures, perform the
CO/PBX Ground Differential Test.
This test determines whether the DC ground potential between the
selected building ground point and the CO ground point is within
acceptable limits by measuring the two currents: “Loop” current and
“Ring” current.