- How to mount the BB-1000 Series enclosures directly to the wall
- 1. Open the front door.
- 2. Mount the backbox to the wall using the four screws provided.
- 1. Place the RAX-LCD-LITE into the backbox, ensure that the mounting holes on the annunciator line up with the studs in the backbox.
- 2. Place the Annunciator Cover Bracket over the RAX-LCD-LITE and use the nuts provided with the backbox to secure the assembly. Refer to the figure below.
- 2.1 Mounting Dimensions
- 3.0 Wiring Instructions
- 4.0 DIP Switch Settings
- 5.0 Specifications and Features
- 6.0 Warranty & Warning Information
16
Specifications and Features
System Reset Button and Indicator
The System Reset button resets the Fire Alarm Control Panel and all Circuits.
Pressing the System Reset button causes a trouble to occur and the LED to illuminate steady yellow.
The following events will occur
• Resets all Latching, Trouble Conditions.
• Resets all Initiating Circuits.
• Resets 4-Wire Smoke Supply and Aux. Power Supply.
• Turns off all Indicating Circuits.
• Turns off Signal Silence, Ack & GA Indicators.
• Turns off Fire Drill.
• Stops and resets all Timers.
• Processes inputs as new events.
• Aux Disconnect is not affected.
• Reset cannot be activated until the Signal Silence Inhibit timer has expired.
Resetting the System clears the indication and turns the LED off.
Building Queue Button and Indicator
Flashes yellow at the Trouble Flash rate when any Building condition is detected on the panel. The
buzzer sounds at the fast rate.
Pressing the Building Queue button allows the user to cycle through and review a list of active Building
Conditions from oldest to most recent. Once all conditions in the queue have been reviewed the LED will
illuminate steady.
Clearing all Building conditions clears the indication and turns the LED off.
Fire Drill Button and Indicator
Illuminates steady yellow during an active Fire Drill.
Pressing the Fire Drill button activates all programmed and non-Disconnected Indicating Circuits. It does
not transmit any Alarms via the City Tie, or Common Alarm Relay.
Fire Drill may be programmed to operate specific NAC Circuits. Fire Drill is cancelled by pressing the
button again (toggle switch), or if the Panel goes into a real Alarm.
General Alarm Button and Indicator - Two Stage Operation or Positive Alarm Sequence
LED and Indicator are active only when the Panel is configured for Two Stage Operation.
LED illuminates steady red when the following occurs:
• Pressing the General Alarm button.
• Activating a General Alarm Initiating Circuit.
• The Auto General Alarm Timer expiring.
Resetting the System clears the indication and turns the LED off.