Phau Ntawv Qhia
Table Of Contents
- Table of Contents
- List of Figures
- List of Tables
- 1.0 Introduction
- 2.0 Mechanical Installation
- 2.1 Mounting Dimensions
- Table 3 BB-1001 Backbox Dimensions
- Table 4 BB-1002 Backbox Dimensions
- Table 5 BB-1003 Backbox Dimensions
- Table 6 BB-1008 Backbox Dimensions
- Table 7 BB-1012 Backbox Dimensions
- How to mount the BB-1000 Series enclosures directly to the wall
- 1. Open the front door.
- 2. Mount the backbox to the wall using the four screws provided.
- 1. Place the RAX-LCD-LITE into the backbox, ensure that the mounting holes on the annunciator line up with the studs in the backbox.
- 2. Place the Annunciator Cover Bracket over the RAX-LCD-LITE and use the nuts provided with the backbox to secure the assembly. Refer to the figure below.
- 2.1 Mounting Dimensions
- 3.0 Wiring Instructions
- 4.0 DIP Switch Settings
- 5.0 Specifications and Features
- 6.0 Warranty & Warning Information
13
DIP Switch Settings
4.0 DIP Switch Settings
Each annunciator assembly (main and adder chassis) needs to be assigned a unique,
sequential Address via the Main Chassis DIP Switch SW1. DIP Switch SW2 is used to allow
disabling of some Front Panel push buttons (when individual switches are “ON” then the
corresponding push button is disabled)
.
4.1 RAX-LCD-LITE DIP switches
4.2 RAX-LCD-LITE Jumpers and Connectors
Set the annunciator “Address” (see the manual for the fire alarm control panel being used), as
follows in the table below:
DIP SWITCH SW1 DIP SWITCH SW2
SW1-1 = Address A0 SW2-1 = Disable System Reset button
SW1-2 = Address A1 SW2-2 = Disable Fire Drill button
SW1-3 = Address A2 SW2-3 = Disable Acknowledge button
SW1-4 = Address A3 SW2-4 = Disable General Alarm button
SW1-5 = Must be set to “OFF” SW2-5 = Not Used
SW1-6 = Not Used SW2-6 =
Disable Auxiliary Disconnect
button
SW1-7 = Not Used SW2-7 = Not Used
SW1-8 =
Must be on for 16 bit
checksum.
SW2-8 = Disable Signal Silence button
P4 Factory Use only.
P5 Connects to RAX-1048TZDS
CONTRAST Adjusts LCD Display’s contrast levels
JW6 EOL Jumper The last RAX-LCD-LITE annunciator in series must have this jumper
set on the pins labeled EOL (the 2 pins on the right).
Table 9 Annunciator Addresses
DIP Switch
Positions
Annunciator Address
1 2 3 4 5 6 7
SW1-1 (A0) ON OFF ON OFF ON OFF ON
SW1-2 (A1) OFF ON ON OFF OFF ON ON
SW1-3 (A2) OFF OFF OFF ON ON ON ON
SW1-4 (A3) OFF OFF OFF OFF OFF OFF OFF
Note: Annunciators on a common RS-485 connection must be numbered sequentially;
i.e.: 1,2,3,4, and not randomly such as 5,3,8, 14! Note that NOT ALL annunciator
“Addresses” are valid for all Fire Alarm Control Panels. Refer to the Fire Alarm
Control Panel Manual for further information
i
firealarmresources.com