Specifications
FleX-Net
TM
Installation and Operation Manual
53
Figure 38: Redundant Wiring for the FNC-2000 Module
Line A
Line D
Line B
Line D
Line C
Line C
Line C
Line B
Line A
Line A
Line A
Line D
Line B
Line B
Line B
Line B
Line D
Line D
Line D
Line C
Line D
Line B
Line C
Line C
Line C
Line A
Line A
Line A
FNC-2000
Lobby Panel
FNC-2000
FNC-2000
FNC-2000
FNC-2000
FNC-2000
FNC-2000
REDUNDANT WIRING
RECOMMENDED CABLE:
BELDEN 5320 UJ or 5320UM
Tyco Pyro CIC
Draka Lifeline
All above cables are 2x18AWG unshielded,
low capacitance
Network Wiring Specifications
Power-Limited and Supervised
Voltage: 9V Max
Current: 800mA
Frequency: 625K Hz
Line Loss: 25 ohms
4000 feet MAX wiring distance
with twisted pair 18 gauge wiring