Specifications
35
Configuration
6.2.3   Charger Settings, Synchronization Settings, NAC Input Settings
Use DIP switch 3 to configure charger, synchronization and NAC Input settings.
Table 7 Charger Settings, Synchronization Settings, NAC Input Settings
DIP switch 3 Switch #
Default Setting = 0  Activated Setting = 1 
Notes/ 
Additional 
Diagrams
1
Charger Cut When all 
NAC’s activated
Charger Always “ON”
Remember
Bit 7 on DIP 
Switch 2 must 
be set to “OFF” 
to enable 
Charger
2-6 Reserve 
7
Independent Mode 
NAC 1 and 2 = Signals 
Configured NAC’s = Sync 
Strobes
Independent Mode 
NAC 1 to 3 = Signals 
Configured NAC’s = Sync 
Strobes
For a 
comprehensive 
description of 
Independent 
Mode options 
see 6.5 
Independent 
Mode 
Configuration 
Options on 
page 62
Independent mode is active if 
SW4 Bit 4-6 Evacuation Rates 
is set to 010, 110, 001, 101, or 011 
AND
SW5 Bit 1-3 Setting Strobe Manufacturer Type set to 100, 
110, 001 or 101. 
8 Synchronous Signal Master Synchronous Signal Slave
Attention: If Independent Mode is not being used SW3-7 must be set to OFF. 
ALL SWITCHES OFF
ALL SWITCHES OFF