Specifications

66
Wiring
7.0 Wiring
This chapter describes the proper field wiring for the FX-3500.
7.1 Wiring Tables
7.1.1 Addressable Loop Wiring Maximums
Advanced Protocol and CLIP Devices
Maximum Loop Current = 350 mA
Maximum Loop Resistance = 40 ohms
Maximum Loop Capacitance = 0.5 μF
Maximum Number of Isolators = 20
7.1.2 RS-485 Wiring to Annunciators and other Devices
Use twisted shielded pair
300mA power limited
22 AWG maximum of 2000 feet
20 AWG maximum of 4000 feet
18 AWG maximum of 8000 feet
Maximum 40 ohm loop resistance
7.1.3 NAC and Auxiliary Power Supply Circuits
Table 19 Advanced Protocol and CLIP Devices Addressable Loop Wiring Table
Wire Gauge Maximum Wiring Run to Last Device
(AWG) ft m
18 3030 923
16 4760 1450
14 7690 2343
12 9820 2993
Table 20 NAC and Auxiliary Power Circuits Wiring Table
TOTAL
SIGNAL
LOAD
MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP
RESISTANCE
18AWG 16AWG 14AWG 12AWG
Amperes ft m ft m ft m ft m Ohms
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2