User Manual

10 (20)
5.0 Disconnecting and Reconnecting a
Circuit (Zone)
You can disconnect and reconnect detection and signal circuits (zones) from the panel using
the bypass options in the menu.
To select the bypass options, you must be in the Command Menu. To enter the Command
Menu, press MENU.
5.1 To Disconnect (Bypass) a Circuit
If you have disconnected (bypassed) a circuit, a trouble message appears on the display and
disappears when the circuit is reconnected.
Step 1: Enter your passcode
1. Enter your passcode.
2. Press ENTER.
Step 2: Select the Bypass menu
1. Use the up and down arrow buttons
to scroll down to “Bypass Det Ckt” or “Bypass NAC
Ckt”.
2. Press ENTER.
3. Use the up and down arrow buttons to select the
circuit that you want to disconnect.
4. Press ENTER.
Step 3: Select BYPASSED
1. Use the up and down arrow buttons
to scroll the cursor to “Bypassed”.
2. Use the right arrow button to change the
selection to “X”. The “X” indicates that the option is
selected.
3. Press ENTER.
4. Press CANCEL twice to return to the main
menu.
Enter the
passcode
ENTER
- Bypass Det
Zone -
2
ABC
8
TUV
ENTER
ENTER
Zone-1
[ ] BYPASSED
2
ABC
8
TUV
6
MNO
ENTER
CANCEL