Specifications

Operating Instructions
8
Operating Instructions
Normal: All indicators are normally OFF except for the green A.C. ON light which illuminates steadily.
Alarm: Operate Alarm Initiating Devices to activate Indicating Appliances. Signals will sound, common alarm will
illuminate red.
Silencing of Alarm: Press Signal Silence button momentarily to silence all audible signals.
Waterflow: Indicating appliances and other output circuits that are activated in response to an alarm initiated by a
designated Waterflow Zone cannot be silenced (manual or automatic).
Supervisory: Activation of any initiating devices for supervisory will sound the buzzer continuously. The Common
supervisory indicator will illuminate amber (steady). The Common Supervisory indicator remains "ON" when the
buzzer is silenced.
System Reset: Press the Reset button momentarily to restore normal operation. All alarm indicators will extinguish
& all latched functions are restored.
Trouble: Any system trouble will sound the buzzer intermittently and common Trouble indicator will flash amber
until the fault is corrected. Specific types of trouble will be indicated by the LCD display by pressing the INFO button.
Call for service.
Fire Drill: Press the Fire Drill button momentarily to sound all audible signals without initiating an alarm. Press the
button again for normal system operation. Note: Auxiliary relays will not operate when Fire Drill is operated.
Lamp Test: Press the Lamp Test button momentarily to test all indicators. All indicators should be lit and buzzer will
sound. Holding down this button will display the firmware version.
CPU Fail LED: Will illuminate amber for an onboard CPU error.
Menu Button: Press the Menu button to access the associated FA-300 Series Fire Alarm Panel. The Menu button
operates as it does on the main FA-300 Series Fire Alarm Panel, refer to the fire alarm manual for further
explanation. Use the keypad arrow keys (2, 4, 6 and 8) to scroll through the menu. Configuration of the fire alarm
panel cannot be accessed from the RAM-300LCD. The Menu button does not operate for the FX-350/351 Series
Fire Alarm Panels.
Enter, Cancel and Info Buttons: The Enter and Cancel buttons are used to input and erase some data for the fire
alarm panel and the Info button is used to view the fire alarm panel logs. The Enter and Cancel buttons do not
operate for the FX-350/351 Series Fire Alarm Panels.
Keypad: The numbered keys and/or letter keys function as they do at the FA-300 Series Fire Alarm Panel, refer to
the fire alarm manual for further explanation. The keypad does not operate for the FX-350/351 Series Fire Alarm
Panels.
Note: The signal silencing function may be inhibited for up to one minute. The Signal silence button will not
operate until the inhibit period has expired.