Appendix D: Power Supply and Battery Calculations (Selection Guide)
Use the form below to determine the required secondary power supply (batteries).
*Assume three Initiating Circuits are in alarm.
'Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
ÒUsing the MPD-65P 2-wire photoelectric smoke detector.
Total Current Requirement:ALARM (B) _____ Amps. (Value obtained from column B)
Battery Capacity Requirement:
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [ ' Alarm in Hr.] _____) = (C) ______AH
Total Alarm Current: Must be 6 amperes or less for FA-300 Series. Indicating Circuits must not exceed 5 amperes.
Battery Selection: Multiply (C) by 1.20 to derate battery.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.
Refer to Appendix A for specifications.
Power Requirements (All Currents are in Amperes)
Model Number Description Qty Standby
Total
Standby
Alarm
Total
Alarm
FA-301-12DDR
Fire Alarm Control Panel,
12 Inp, 4Out with UDACT
Using 3K9 resistors
X 0.174
= 0.444 =
FA-301-12DDR
Fire Alarm Control Panel,
12 Inp, 4Out with UDACT
Using active resistors
X 0.104
= 0.394 =
FA-300-6DDR
Fire Alarm Control Panel, 6
Inp, 2 Out with UDACT
Using 3K9 resistors
X 0.142
= 0.312 =
FA-300-6DDR
Fire Alarm Control Panel, 6
Inp, 2 Out with UDACT
Using active resistors
X0.112
= 0.282 =
FA-300-6DR
Fire Alarm Control Panel, 6
Inp,2 Out without UDACT
Using 3K9 resistors
X 0.142
= 0.312 =
FA-300-6DR
Fire Alarm Control Panel, 6
Inp, 2 Out with UDACT
Using active resistors
X0.112
= 0.282 =
ICAC-306
Det Class A Converter
Adder Module
X 0.000
-0.000 0.000 -0.000
OCAC-304
Sig Class A Converter
Adder Module--4 Circuits
X 0.000
-0.000 0.000 -0.000
OCAC-302
Sig Class A Converter
Adder Module--2 Circuits
X 0.000
-0.000 0.000 -0.000
PR-300
Polarity Reversal and City
Tie Module
X 0.050
=
0.300
(City Tie in Use)
=
RM-312 12 Relay Adder Module X 0.000
= 0.160 =
RM-306 6 Relay Adder Module X 0.000
= 0.080 =
SRM-312 Smart Relay Module X 0.030
= 0.140 =
RAM-300LCD Smart Remote Annunciator X 0.016
= 0.040 =
RAM-208/216 Remote Annunciator X 0.035
= 0.090/0.140 =
RTI-1 Remote Trouble Indicator X 0.035
= 0.035 =
Two-Wire Smoke Detectors X Ò 0.00011
= * 0.090 = 0.090
Four-Wire Smoke Detectors X
= =
Signal Load (bells, horns, strobes, and etc.) X
=
Auxiliary Power Supply for Annunciators, etc.
=
=
Total currents (Add above currents) STANDBY (A)ALARM(B)