Installation manual
Appendix C: Specifications
68
Appendix C: Specifications
FA-300 Fire Alarm Control Panel (LCD) RM-312/306 Relay adder module
Digital Signal Processor (DSP) based design. Fully configurable
using front panel LCD display with Password Access.
Electrical Ratings
AC line voltage
120 VAC 60 Hz 3 amps\ 240 VAC 50 Hz 1.5A (primary)
Power Supply Rating
6 amps maximum (secondary)
Battery
Type: 24VDC Gel-Cell/Sealed lead acid
Charging capability: 10AH
Protection: 10A on board (F1) slow blow micro fuse
Indicating circuit
4 supervised style Z (Class B) indicating circuits, configured as
normal or visual. Terminals are labeled “SIG”.
Power limited / 24VDC unfiltered / 1.7A @ 49C per circuit
Max power allowed = 5A
- 1.7A (aux power unfiltered if used)
- 0.5A (aux power filtered if used)
- 0.3A (4-wire smoke power if used)
if no auxiliaries are used the max power is 5A
Current consumption Standby 283mA/Alarm 560mA
Aux supply (non resettable)
Must be connected to a listed power-limited source of supply
Contact rating NO / NC / 28VDC per contact / 1A resistive load
max
Current consumption standby 0mA / alarm (RM-312) 160mA /
alarm (RM-306) 80mA
ICAC-306 Input Class A Converter module
Standby 0mA / alarm 0mA
OCAC-304 Output Class A Converter module
Standby 0mA / alarm 0mA
OCAC-302 Output Class A Converter module
Standby 0mA / alarm 0mA
SRM-312 Smart Relay Module
Must be connected to a listed power-limited source of supply
Contact rating NO/NC / 28VDC per contact / 1A resistive load
max
Current consumption standby 30mA / alarm 140mA
RAM-300 Remote LCD Annunciator
Standby 16mA / alarm 40mA
RAM-208 8 Zone Remote Annunciator
Standby 35mA / alarm 90mA
power limited / 22.3VDC regulated / 500mA max
Remote Trouble Indicator
4-wire smoke supply (resettable)
Standby 35mA / alarm 35mA
Power limited/22.3Vdcregulated / 300mA max
Polarity reversal and city tie module
Unfiltered supply (full wave rectified)
Power limited / 24VDC unfiltered / 1.7A max at 49C
Auxiliary Relays (Common alarm/supv/trb/ and
auxiliary second alarm)
Must be connected to a listed power-limited source of supply
FormC / 28VDC / 1A max
Initiating circuit
12 supervised style B (Class B) initiating circuits, configurable
(normal or verified). Terminals are labeled “DET”. Compatibility
ID “A”
Power limited / 19VDC reg. / 3mA for detectors / 0.15Vp-p ripple
/ 40mA max (alarm short)
1 RS-485 Connection
For remote annunciators. Terminals are labeled “RS-485”.
PR-300 Polarity reversal city tie module (optional)
RM-312/306 Relay Module (optional)
City tie power limited / 24VDC unfiltered / 250mA max / 14Ohms
trip coil
Polarity reversal power limited / 24VDC open / 12VDC at 3.5mA /
8.5mA max (shorted)
Polarity reversal supv terminal
24VDC (normal) / -24VDC (supervisory) / 0V (trouble)
Polarity reversal alarm terminal
24VDC (normal) / -24VDC (alarm) / 0V (trouble)
Current consumption standby 50mA / alarm 300mA (city tie in
use) / alarm 70mA (city tie not in use)
System Model: FA-300 Series LCD Version Fire Alarm Control Panel
System Type: Local, Auxiliary (using PR-300), Remote Protected Premise Station (using PR-300 or
FA-301-12DDR or FA-300-6DDR) Central Station Protected Premises (using FA-301-12DDR or
FA-300-6DDR)
Type of Service: A, M, WF, SS
Type of Signalling: Non-Coded
Applicable Standards: NFPA 70 and 72, UL-864 Rev. 9