Installation manual
FA-300 Series LCD Version Installation and Operation Manual
63
Supervised auxiliary supply
The supervised auxiliary supply is supervised for shorts. When a short is detected on supervised aux supply the
power is cut off and a trouble message is generated. Press the system “RESET” key to restore power to the
system. If the short is removed, the panel will return to normal; otherwise the trouble message will stay.
City tie Polarity reversal - PR-300/ Relay module
The city tie or polarity reversal module is supervised for open and whether or not the PR-300 is plugged in. The
relay module is supervised for whether or not it is plugged in.
If any of the modules are not plugged in, the following trouble message is generated:
Note: The trouble code and info is for trained service personnel only.
"INFO " Key
Aux. Power Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
"INFO " Key
CtyTie/RM312 missing
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info